Translate
Sunday, 12 August 2012
TRANSDUCERS IN ELECTRICAL POWER SYSTEMS ENGINEERING PROTECTION
TRANSDUCERS
CONVERT HIGH VOLTAGES AND CURRENT TO LOWER VALUES FOR THE FOLLOWING REASONS
1) THE LOWER LEVEL INPUT TO THE RELAYS ENSURE THAT THE PHYSICAL HARDWARE USED TO CONSTRUCT THE RELAYS WILL BE QUITE SMALL AND THUS LESS EXPENSIVE.
2) THE PERSONNEL WHO WORK ON THE RELAYS WILL BE WORKING IN A SAFE ENVIRONMENT
IN PRINCIPLE, THE TRANSDUCERS ARE SAME AS THE POWER TRANSFORMERS; PUT TO SPECIFIC USE.
The current transformer is expected to produce a current in the secondary winding which duplicates the primary current waveform as faithfully as possible.
THE AMOUNT OF POWER DELIVERED BY THESE TRANSFORMERS IS RATHER MODEST SINCE THE LOAD ON THEM IS EITHER RELAY AND METER AND USED ONLY WHEN NEEDED.
THIS LOAD ON CT AND VT IS REFERRED TO AS THEIR BURDEN.
BURDEN :
THE IMPEDANCE CONNECTED TO THE TRANSFORMER SECONDARY WINDING.
IT MAY ALSO BE REFERRED TO AS THE VOLTAMPERE DELIVERED TO THE LOAD.
IE. IT MAY ALSO REFER TO THE VOLTAMPERE DELIVERED TO THE LOAD.
EG.
A TRANSFO RMER DELIVERING 5 AMPERES TO A RESISTIVE BURDEN OF 0.1 OHM CAN BE SAID TO HAVE A BURDEN OF 2.5VA VOLTAMPERES AT 5A, 5AMPERES.
CT CURRENT TRANSFORMER
CURRENT TRANSFORMERS HAVE RATIO ERRORS WHICH CAN AND ARE CALCULATED IN SOME CASES AND IN OTHER CASES HAVE TO BE MEASURED.
IF IMPEDANCE BURDEN IS LARGE, THIS ERROR CAN BE HIGH. IF THE CT IS PROPERLY SELECTED WITH RESPECT TO THE BURDEN, THIS ERROR CAN BE MINIMIZED.
CT BUILT WITHIN THE BUSHING THROUGH WHICH A TERMINAL OF THE POWER EQUIPMENT IS BROUGHT OUT……………ARE ALSO AVAILABLE
HENCE CALLED BUSHING CT’S
EQUIPMENT ENCLOSED IN GROUNDED TANKS FILLED WITH OIL INSULATING MEDIUM…….. ARE ALSO AVAILABLE
THIS TYPE IS AVAILABLE IN DEAD - TANK SYSTEMS.
EHV (- SWITCHING STATIONS) HERE LIVE – TANK CB ARE IN USE, FREE STANDING CURRENT TRANSFORMERS
CT CURRENT RATING STANDARDISED AT 5A SECONDRIES.
SECOND STANDARD 1A IN EUROPE
FOR SHORT PERIODS, YOU CAN HAVE 10-20 TIMES THAT DURING SHORT CIRCUIT IN SECONDARY.
CT RATIOS RANGE FROM
50: 5 - 1200: 5
CURRENT RATIO
CURRENT TRANSFORMER RATIOS
CURRENT TRANSFORMER RATIOS A:A
50A:5A
100A:5A
150A:5A
200A:5A
250A:5A
300A:5A
400A:5A
450A:5A
500A:5A
550A:5A
600A:5A
650A:5A
700A:5A
750A:5A
800A:5A
850A:5A
900A:5A
950A:5A
1000A:5A
1050A:5A
1100A:5A
1150A:5A
1200A:5A
BURDEN
BECAUSE IF FOR EXAMPLE
5 AMPERES IS DELIVERED BY A TRANSFORMER TO A RESISTIVE BURDEN OF 0.1OhM(Ω)
THE TRANSFORMER MAY ALSO BE SAID TO HAVE A BURDEN OF 2.5 VOLTSAMPERES AT 5 AMPERES.
THIS IS BECAUSE GIVEN V=IR
V = .5V FOR I = 5A AND R =0.1Ω(Ohms)
HENCE
VI = .5X5 = 2.5VA
VOLTAGE TRANSFORMER
TWO TYPES EXIST
1) FOR LOW - VOLTAGE APPLICATION
SYSTEM VOLTAGES 12 Kv or LOWER
PRIMARY WINDING AT SYSTEM VOLTAGE AND SECONDARY WINDING AT 67V
(THIS REPRESENTS SYSTEM LINE TO NEUTRAL VOLTAGE )
67V*√3 = 116V
REPRESENTING THE SYSTEM LINE TO LINE VOLTAGE )
ARE AN INDUSTRIAL STANDARD.
THIS IS SIMILAR TO A MULTIWINDING POWER TRANSFORMER AND BECOMES EXPENSIVE AT HIGHER SYSTEM VOLTAGES.
AT HV AND EHV LEVELS, A CAPACITANCE POTENTIAL – DIVIDER CIRCUIT IS USED.
C1 AND C2 ARE ADJUSTED SO THAT A VOLTAGE OF A FEW kV IS OBTAINED ACROSS C2 WHEN TERMINAL A IS AT SYSTEM POTENTIAL.
IN SUCH A COUPLING CAPACITOR VOLTAGE TRANSFORMER (CVT) THE TAPPED VOLTAGE IS FURTHER REDUCED TO RELAYING VOLTAGE LEVEL BY A TRANSFORMER.
CIRCUIT DIAGRAM OF A CAPACITOR – COUPLED VOLTAGE TRANSFORMER CVT WITH ITS TUNING INDUCTANCE L.
IN SUCH A COUPLING CAPACITOR VOLTAGE TRANSFORMER (CCVT) (CVT) THE TAPPED VOLTAGE IS FURTHER REDUCED TO RELAYING VOLTAGE LEVEL BY A TRANSFORMER.
THE VOLTAGE AT POINT A CAN BE CONSIDERED TO BE THAT OF AN INFINITE BUS SO FAR AS THE CONNECTED CAPACITORS ARE CONCERNED.
Subscribe to:
Post Comments (Atom)
this site needs advancement
ReplyDelete