MODIFICATION
THE CHARACTERISTIC CIRCLE CENTRED AT THE ORIGIN CAN BE
OFFSET BY AN AMOUNT Z’
Z - Z’ < |Zr| TRIP
Z - Z’ > |Zr| BLOCK
BY MAKING | Z’| =
| Zr| THE
CHARACTERISTIC CAN BE MADE TO PASS THROUGH THE ORIGIN.
THIS IS KNOWN AS THE MHO CHARACTERISTIC
A FAULT TO THE LEFT OF THE BUS 1 NO MATTER HOW CLOSE TO THE
BUS WILL NOT RESULT IN A TRIP DECISION
BECAUSE
Z = V1/I12
AND WILL LIE IN THE THIRD QUARDRANT.
ZONE OF A RELAY INCLUDES ALL OF THE POWER SYSTEM THAT IS
SITUATED IN ONLY ONE DIRECTION FROM THE RELAY LOCATION
R21 OPERATES FOR FAULT LEFT OF ITS LOCATION.
REMEMBER THAT THE ELECTRICAL POWER LINE IS PREDOMINANTLY A
REACTIVE LINE
FAULT LEFT OF R21
FAULT CURRENT FROM 2 TO 1 TO LEAD VOLTAGE AT BUS 2 BY 90o
THE OPERATION:
DEPENDS ON THE DIRECTION OF CURRENT WITH RESPECT TO THE
VOLTAGE.
THE QUANTITY THAT PROVIDE THE REFERENCE PHASOR IS CALLED A
POLARIZING QUANTITY.
IN THIS CASE A POLARIZING VOLTAGE.
SOMETIMES, CURRENT IS USED.
Θmin
> θop > θmax TRIP
Θmin
< θop < θmax BLOCK
θop
: PHASE ANGLE OF OPERATING
QUANTITY MEASURED WITH THE POLARIZING PHASOR AS REFERENCE
Θmin
, θmax :TWO
ANGLES DEFINING THE BOUNDRY OF THE OPERATING CHARACTERISTICS.
DIRECTIONAL RELAY
RELAY PERFORMANCE CHARACTERISTICS IN THE COMPLEX PLANE OF
THE PHASOR DIAGRAM IS DIVIDED.
THE SHADED PART WILL TRIP
BACKUP PROTECTION